1-1 |
General |
1-1/1 |
Address: this list is known as the list of ‘safety requirements from fire’, and it s referred to in this document as ‘list’ or this list’. |
1-1/2 |
Purpose: the purpose of this list is to specify the minimum requirements of safety against fire to protect the souls of the users of the building, without impeding their daily using of the premise. |
1-1/3 |
Field: |
1-1/3/1 |
This list is concerned in the requirements of soul saving from fire and any relative emergency case. |
1-1/3/2 |
Take into consideration that in this list is that the panic situation is caused because of fire in the building, through the requirements designed to eliminate panic in emergency times. |
1-1/3/3 |
To take into consideration while setting this list the following points: |
1-1/3/3/1 |
The ability of the structural construction in resisting fire. |
1-1/3/3/2 |
Kinds and levels of fire. |
1-1/3/3/3 |
The type of those who uses the building and how much they count. |
1-1/3/3/4 |
Kind of activities that are carried in the premises. |
1-1/3/4 |
To put in the list the minimum requirements for designing the ways to escape (emergency exits) for the users of e building to a safer places whether it was inside or outside the building. |
1-1/3/5 |
It was taken into accounts that the escaping ways weren’t the only factor in [reserving lives that are mentioned in the list, as for the list doesn’t address all the considerations, for example it doesn’t deal with public awareness that is considered one of the factors of preserving lives. |
1-1/3/6 |
The list doesn’t take into account personal accidents such as falling on the ground, which is caused by the lack of awareness of the users to the safety terms. As well as the list focused on soul preserving from fire as a basement of its requirements, on the contrary to the property preservation. |
1-1/3/7 |
This regulation is not a list on the conditions of constructions, but t is used with the list of orders of structure. |
1-1/3/8 |
This list is not being set to preserve the souls of those who intend or by accident set on fire, or those that are near the fire location. |
1-1/4 |
Application procedures: |
1-1/4/1 |
This list is applied on all the buildings that get its license after the starting of this list. |
1-1/4/2 |
It’s not practical in most of the time to apply this list on the existing buildings, and in such a case the civil defense has the right to request for more equipments or alternatives for some preventive precautions in accordance to this regulation. |
1-1/4/3 |
The civil defense has the right when he get the license for constructing or operating to ask for extra equipments or alternatives for some preventive precautions in accordance to this regulation. |
1-1/4/4 |
Any new additions for the exiting building must be subjected to the requirements and conditions of these terms. |
1-1/4/5 |
When a building contains two or more activities or using and in which they vary in their level about danger, and in which we can’t separate, in this case the requirements that mostly ensure safety will be applied on the activities or different using. |
1-1/4/6 |
None of the requirements are forbidden concerning the design, installing, using better kinds to protect from fire, making more than one emergency exits, or any tools that may positively affect on the protection of the users, or any other equipments that will have the same role as mentioned by the terms, under a condition that it should provide the civil defense with the necessary documentaries that ensure the efficiency of the alternative. |
1-1/4/7 |
The system, equipments, ad tools of protection must be maintained to ensure its permanent and high efficient work. |
1-1/5 |
Operating and the using of the building: |
1-1/5/1 |
The buildings that have its constructional license after the work of his list, is prohibited from being used if it was contrary to the requirements of this regulation. |
1-1/5/2 |
The buildings that exist before these regulations can be used under a condition that they should have the following terms: |
1-1/5/2/1 |
There shouldn’t be a real apparent danger that affect the lives of he users. |
1-1/5/2/2 |
The classification and activity of the building must not change, for if there were any changes then the terms must be applied directly. |
1-1/5/2/3 |
As long as the escape ways are still available, and the safety system against fire works as usual, so the building could be used during it maintenance or during its fixing period. |
1-1/6 |
the principles of design: |
1-1/6/1 |
The aim of this list as it was mentioned before focuses on the safety of the users, without impeding any of their daily use, and this goal is reached through ensuring to apply at least the minimum of the safety requirements to protect from fire. And here is some points: |
1-1/6/2 |
Must take into account that the structure and the building must be designed, well coordinate, supporting, and safeguarded to avoid the lives of the users the danger of fire, smoke, fumes and panic in emergency situations, and to allow the users to evacuate the building in cases of fire. |
1-1/6/3 |
Make sure the structure of the building is capable of handling the effects of fire during the evacuation period from the users. |
1-1/6/4 |
Make sure during designing the building and before constructing it that the escape ways (emergency exits) are available and fits every building or facility, concerning the number, capacity, location, rise, kinds of substances used, and to take into consideration the type of the building, its users, and safety equipments against fire. |
1-1/6/5 |
To ensure that the emergency exits do exists and not through counting on the ways to fight fire. |
1-1/6/6 |
Its not always necessary, to totally evacuate the building to escape fire, for there might be in the building a horizontal evacuating zone that is protected from fire, gas leaks from the floors or any other part of the building. These places provide a relative safety up till the emergency case is over. |
1-1/6/7 |
During deign make sure that the escaping ways are free from any obstacle and the way the doors open goes with the way of escape. |
1-1/6/8 |
Make sure to put the signs that show the escaping ways in order to prevent confusion during the evacuation period. |
1-1/6/9 |
Make sure that there will be enough lights, alarm system that fits with the building, and the isolation of the vertical openings from the rest of the building. |
1-1/6/10 |
Make sure that the minimum safety requirements are available. |
1-1/6/11 |
Give more chances in the design process in order to provide more protection to keep on using the building, |
1-2 |
Classification of the buildings and facilities, |
1-2/1 |
Buildings are classified in two ways: first through the nature of its use, second according to the dangers of its contents. |
1-2/1/1 |
The facilities are classified according to the nature of its usage into the following groups: |
1-2/1/1/1 |
Collective buildings |
1-2/1/1/2 |
Educational buildings |
1-2/1/1/3 |
Health and social care premises |
1-2/1/1/4 |
Residential buildings |
1-2/1/1/5 |
Commercial buildings and public markets |
1-2/1/1/6 |
Industrial and industrial occupational buildings |
1-2/1/1/7 |
Storage building and parking |
1-2/1/1/8 |
Building of special character |
1-2/2 |
Each of the groups have several types of buildings that have similar activities and collectives, such as: |
1-2/1/1/1 |
Collective buildings: are the buildings or part of them that are specified in the gathering of fifty people for the purpose of entertainment, culture, or sports like: |
1-2/1/1/2 |
Educational buildings: it is for the purpose of teaching, and it contains six regular time students at least four hours a day and not less than twelve hours a week, such as kindergartens, pre-primary schools, elementary up till secondary schools, and vocational schools. |
1-2/1/1/3 |
The health and social care premises: it is for the purpose of the health and social care in which its users are incapable of movement or they are under arrest, as well as the hospitals and elderly care home, kindergartens, children social; welfare and that of the mental health and prison. |
1-2/1/1/4 |
Residential buildings: it is specified for housing or accommodation. The residential buildings are divided into several categories according to the type of exploitation: |
1-2/1/1/4/1 |
Buildings consisting of permanent housing units for the same family (apartments) such as housing investments. |
1-2/1/1/4/2 |
Buildings consisting of rooms or dormitories for permanent individual or collective housing such as students’, staff’s workers’, and soldiers’ housing. |
1-2/1/1/4/3 |
Buildings consisting of rooms for temporary accommodation with or without paying such as hotels, motels, guest house, and furnished apartments. |
1-2/1/1/4/4 |
Private housing such as small villas or private castles. |
1-2/1/1/5 |
Commercial buildings and public markets: it is for public service (shops), or that its users do not exceed 50 people at one time and it is specialized for the usage of offices. Stores wholesale and retails, occupational services such as: shopping centers, tailoring hairdressing shops, supermarkets, photography shops, business and service offices, small banks, institutional offices, company offices, consulting and engineering offices, and real estate offices. |
1-2/1/1/6 |
Industrial facilities and industrial shops: it is specified in industrial purposes in which there s installation, mixing, and packaging, or where reforms takes place in the industrial occupations, including: |
1-2/1/1/7 |
Storage buildings and parking it is for storing raw materials, the manufactured products, or semi processed. |
1-2/1/1/8 |
Buildings of special characters: are those buildings that contain different types of premises such as towers, high buildings, cellars (underground buildings). |
1-2/1/2 |
Facilities are classified according to the danger of its contents to the following categories: light danger, medium danger, and high danger. |