10-6/6 |
Corridors: You must provide the general conditions of the corridors as it came in the section ways to escape (emergency exits). Under a condition that the width of the corridors must not be less than (2m) and the secondary not less than (1.5). |
10-6/6/1 |
If industry place were not fixed or permanent, and the corridors are unclear, the corridors must be planned with a reflector paint, to clarify the corridors and work spaces or storage. |
10-6/7 |
Exits: conditions of section III "for ways to escape (emergency exits) must be provided in addition to these conditions. |
10-6/7/1 |
The number of exits must be in accordance with the general conditions of not less than two abroad directors to the parties of the building and on the outer wall, each leading to the outside. |
10-6/7/2 |
all exits must lead to the outside directly, or to the stairs or safe corridor against fire which is separated from the building with an isolating space. |
10-6/7/3 |
only one way out in the industrial buildings might be accepted if it has a medium degree of danger, with the approval of civil defense, if the following conditions: |
10-6/7/3/1 |
The depth or direct distance inside the section must not exceed 15m. |
10-6/7/3/2 |
The transition distance to the exit or the safe stairs should not be more than 30m. |
10-6/7/3/3 |
The transition distance to the closed ends must not go beyond 7.5m. |
10-6/7/3/4 |
The conditions concerning the escaping ways must be provided especially the stairs. |
10-6/8 |
Stairs: You should apply the terms of Title III "ways of escape (emergency exits)", in addition to these conditions. |
10-6/8/1 |
It must not be less than two stairs for each floor, far apart from each other to the parties of the building and the outside wall, each leading directly to the outside. |
10-6/8/2 |
The stairs must be protected and kept away from the building with an isolated space protected from fire and lead directly to the outside. |
10-6/8/3 |
Civil Defense may accept the presence of one stair in the industrial building that has a medium degree of seriousness in case all the safety conditions of the building are available. |
10-6/9 |
Final exit: In all cases, the escape ways should lead all the way out to the final exit that leads directly to the outside |
10-6/10 |
Sections of other uses, if the industrial buildings have a high-risk of seriousness then the applied conditions must be those that are specified to such a situation or conditions with higher procedures of safety. |
10-7 |
Fire-fighting equipment and warning: You must provide the requirements of Section IV, "General requirements for engineering services" in addition to the conditions contained in table 10-4. |
10-7/1 |
The fire equipments and alarms must be in terms of design, implementation and maintenance in accordance with the special requirements of the equipments and fire warning or civil defense guide. |
10-7/2 |
The ways of struggling fire differ according to the difference in the industrial occupation and the used substances, for this the fire equipments and alarm systems vary from one factory to another, and this is revealed in table 10-4 that shows the minimum average of the requirements, and that the civil defense can ask for more equipments according to the necessity of the situation. |
10-7/3 |
Civil defense may request additional equipment or alternative for some preventive precautions required in accordance to the conditions. |